About Siemens MM430 inverter F002 alarm failure, the analysis is as follows -
1. F0002 is an overvoltage fault.
2, the cause of the failure -
1) The voltage of the DC link (r0026) exceeds the trip level (P2172);
2) The overvoltage is caused by the power supply voltage being too high or the motor is in the regenerative braking mode;
3) The ramp is falling too fast, or the motor is rotated by the large inertia load and is in regenerative braking state.
3, the solution -
1) Check the power cable and motor grounding of the motor to see if there is any broken cable or improper grounding.
2) Increase the values ​​of the ramp parameters P1120 and P1121 of the inverter.
3) Are you equipped with a braking resistor? If not configured, please pay attention to setting parameter P1240=1; if the braking resistor is configured, please pay attention to setting parameter P1240=0.
4) If your working conditions require faster braking performance and frequent braking, it is recommended that you configure the braking resistor (if you do not currently have it).
As a result of advanced microprocessor and unique choDiscovery echo processing technology, guided wave radar level meter can be used in a variety of complex conditions.Because of the type of process connections and detection components, making 70X Series Guided Wave Radar Level Meter is suitable for a variety of complex conditions and applications. Such as: high temperature, high pressure and low dielectric constant media.Pulsed work, guided wave radar level instruments transmit power is very low, can be installed in a variety of metals, non-metallic container, no harm to humans and the environment.